SERVICE MANUAL
CONTENTS
1. TECHNICAL CHANGES ··································· 3
2. PART NAMES AND FUNCTIONS ····················· 3
3. SPECIFICATION ················································ 4
4. OUTLINES AND DIMENSIONS ························ 6
5. WIRING DIAGRAM ············································ 7
6. REFRIGERANT SYSTEM DIAGRAM ··············· 8
7. DATA ·································································· 9
8. ACTUATOR CONTROL ··································· 15
9. SERVICE FUNCTIONS ··································· 16
10. TROUBLESHOOTING ····································· 16
11. DISASSEMBLY INSTRUCTIONS ···················· 32
Wireless type
Models
MUZ-FD09NA
MUZ-FD09NA-
U1
MUZ-FD12NA
MUZ-FD12NA-
U1
OUTDOOR UNIT
Indoor unit service manual
MSZ-FD•NA Series (OBH497)
NOTE:
RoHS compliant products have <G> mark on the spec name plate.
TM
HFC
utilized
R410A
No. OBH498
PARTS CATALOG (OBB498)
Seitenansicht 0
1 2 3 4 5 6 ... 35 36

Inhaltsverzeichnis

Seite 1 - SERVICE MANUAL

SERVICE MANUALCONTENTS1. TECHNICAL CHANGES ··································· 32. PART NAMES AND FUNCTIONS ····················· 33. SPECIFICATION ··

Seite 2

10107-2. PERFORMANCE CURVE657075757065121068Indoor intake air DB temperature (°F)= 381 CFMAirflow15 25 35 45 55Outdoor intake air WB temperature (°F)0

Seite 3 - PART NAMES AND FUNCTIONS

11117-3. CONDENSING PRESSURECoolingData is based on the condition of indoor humidity 50 %.Air flow should be set to High speed.MUZ-FD12NA(PSIG)Condens

Seite 4 - SPECIFICATION

757065(PSIG) (PSIG)Condensing pressureOutdoor ambient temperature14 20 25 30 35 40 45 50 55 60 65 70(°F)220200180160140240260280320300340360380400Indo

Seite 5 - Test condition

13137-4. STANDARD OPERATION DATAModel MSZ-FD09NA MSZ-FD12NAItem Unit Cooling Heating Cooling Heating TotalCapacity Btu/h 9,000 10,900 12,000 13,600SHF

Seite 6 - OUTLINES AND DIMENSIONS

147-5. CAPACITY AND INPUT CORRECTION BY INVERTER OUTPUT FREQUENCYCapacity correction factorsInput correction factorsInput correction factorsCapacity c

Seite 7 - WIRING DIAGRAM

15158ACTUATOR CONTROLMUZ-FD09NAMUZ-FD12NA8-2. R.V. COIL CONTROLHeating . . . . . . . . . . . . . . . . . ON Cooling . . . . . . . . . . . . . . . . .

Seite 8 - REFRIGERANT SYSTEM DIAGRAM

16SERVICE FUNCTIONS99-1. CHANGE IN DEFROST SETTING Changing defrost finish temperature <JS> To change the defrost finish temperature, cut/sold

Seite 9

17Outline of the functionThis air conditioner can memorize the abnormal condition which has occurred once.Even though LED indication listed on the tro

Seite 10

18Does POWER lamp on the indoor unit blink at the interval of 0.5 seconds?Blinks: The outdoor unit is abnormal. Beep is emitted at the same timing as

Seite 11 - Indoor DB temperature (°F)

19 3. Outdoor unit failure mode tablePOWER lamp(Indoor unit) Abnormal point (Failure mode / protection) LED indication(Outdoor P.C. board) Conditio

Seite 13 - 7-4. STANDARD OPERATION DATA

2010-3. TROUBLESHOOTING CHECK TABLENo. Symptom LED indication Abnormal point/ Condition Condition Correspondence 1Outdoor unit does not oper-ate. 1-t

Seite 14 - Heating total input

21No. Symptom LED indication Abnormal point/ Condition Condition Correspondence 18Outdoor unit operates. 7-time fl ash 2.5 seconds OFF Low discharge t

Seite 15 - ACTUATOR CONTROL

22Part name Check method and criterion FigureDefrost thermistor (RT61) Ambient temperature thermistor (RT65)Outdoor heat ex-changer temperature ther

Seite 16 - TROUBLESHOOTING

2310-5. TROUBLESHOOTING FLOWAre the voltages balanced?Disconnect the connector (CN61) between compressor and the intelligent power module (IPM).Replac

Seite 17

24 F Check of compressor start failure D Check of compressor winding E Check of compressor operation time●Disconnect the connector (CN61) between t

Seite 18 - Operational procedure

25Is the thermistor normal? (Refer to 10-6.1.)Reconnect the connector of thermistor.Turn ON the power supply and press EMERGENCY OPERATION switch. NoR

Seite 19

26 I Check of outdoor fan motorOutdoor fan motor does not operate. J Check of power supplyInverter does not operate.Is the outdoor fan motor normal?

Seite 20

27Press OPERATE/STOP (ON/OFF) button of the remote controller (the set temperature is displayed) with the remote controller headed towards the indoor

Seite 21

28Check the outdoor fan motor. (Refer to10-5. .)Is the fuse (F901) blown on the in-verter P.C. board?Check the connection of the connectors (CN932) of

Seite 22 - MUZ-FD09NA MUZ-FD12NA

29 M How to check miswiring and serial signal error (outdoor unit does not work)• Unit cannot operate neither by the remote controller nor by EMERGEN

Seite 23 - C Check of compressor

331TECHNICAL CHANGESMUZ-FD09NAMUZ-FD12NAMUZ-FD09NA - U11. New modelPART NAMES AND FUNCTIONS2MUZ-FD09NAMUZ-FD12NAMUZ-FD12NA - U1Air outletDrain outletP

Seite 24

30 N Electromagnetic noise enters into TV sets or radiosYesIs the unit grounded?NoGround the unit.YesIs the distance between the antennas and the ind

Seite 25 - H Check of R.V. coil

3110-6. TEST POINT DIAGRAM AND VOLTAGE-4 14 32 50 68 86 1040102030405060708090100Temperature(°F)Defrost thermistor(RT61)Ambient temperature thermistor

Seite 26 - J Check of power supply

32OPERATING PROCEDURE PHOTOS1. Removing the cabinet(1) Remove the screw fixing the service panel. (See Photo 1.)(2) Pull down the service panel and re

Seite 27

33OPERATING PROCEDUREPHOTOS2. Removing the inverter assembly, inverter P.C. board(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the le

Seite 28

34OPERATING PROCEDUREPHOTOS5. Removing outdoor fan motor(1) Remove the cabinet and panels. (Refer to 1.)(2) Disconnect the connectors for outdoor fan

Seite 30

HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN Copyright 2008 MITSUBISHI ELECTRIC ENGINEERING CO.,LTDDistributed in Ja

Seite 31 - MUZ-FD09NA MUZ-FD12NA

443SPECIFICATIONOutdoor unit model MUZ-FD09NA MUZ-FD12NA Capacity Rated (Minimum~Maximum) Cooling 1Btu/h 9,000 (2,800~9,000) 12,000 (2,800~12,000)Hea

Seite 32 - DISASSEMBLY INSTRUCTIONS

55Test conditionARI Mode Test Indoor air condition Outdoor air condition Dry bulb (°F) Wet bulb (°F) Dry bulb (°F) Wet bulb (°F) SEER (Cooling)

Seite 33 - OPERATING PROCEDURE

66OUTLINES AND DIMENSIONS4Unit: inchMUZ-FD09NAMUZ-FD12NALiquid pipe :1/4 (flared)Gas pipe :3/8 (flared) 6-23/3225-7/82-23/321-3/415-3/412 ~ 12-3/413

Seite 34

775WIRING DIAGRAMMUZ-FD09NA MUZ-FD12NA

Seite 35

86REFRIGERANT SYSTEM DIAGRAMUnit:inchMUZ-FD09NAMUZ-FD12NAOutdoorheatexchangerFlared connectionDefrostthermistorRT61DischargetemperaturethermistorRT62S

Seite 36 - Made in Japan

9DATA7MUZ-FD09NA MUZ-FD12NA7-1. PERFORMANCE DATA 1) COOLING CAPACITYModel Indoor air Outdoor intake air DB temperature (˚F) IWB 75 85 95 105 115(˚